Cъемная аккумуляторная батарея S8BA
- Использование литий-ионной аккумуляторной батареи, которая отличается увеличенным сроком службы, позволяет сделать конструкцию легче и компактнее.
- Встроенный блок клемм для обеспечения питания интерфейса ввода-вывода.
- Одновременное отключение с промышленным компьютером или контроллером выполняется посредством порта ввода-вывода ИБП USB/RS- 232C.
Характеристики и информация для заказа
Model Number Legend
Use the following format to place an order. The control unit and battery unit are separate, and the battery unit is sold separately.
Control unit part
1. Input voltage specification | 2. Output voltage | 3. Capacity | |||
Code | Input voltage specification | Code | Output voltage | Code | Capacity |
24D | 24 VDC | 24D | 24 VDC | 480 | 480 W |
960 | 960 W |
Battery unit part
1. Battery type | 3. Terminal block shape | ||
Code | Type | Code | Terminal block shape |
S | Separated battery type | 480 | 480 W |
960 | 960 W |
Ordering Information
Uninterruptible Power Supply (UPS)/Control Unit Part
Input voltage | Output voltage | Output current/capacity | Order code |
24 VDC | 24 VDC | 20 A/480 W | S8BA-24D24D480SBF |
40 A/960 W | S8BA-24D24D960SBF |
Battery unit part
Rated voltage | Rated capacity | Weight | UPS Model: Required units | Order code |
25.2 VDC | 3900 mAh | 1.5 kg | S8BA-24D24D480SBF | S8BA-S480L |
25.2 VDC | 7800 mAh | 2.5 kg | S8BA-24D24D960SBF | S8BA-S960L |
Communication cable
Specifications | Type | Length | Order code |
For RS-232C port | RJ45/Dsub9Pin | 2 m | S8BW-C01 |
For CONTACT port | RJ45/Discrete wire | S8BW-C02 |
Specifications
Description | Capacity | 480 W | 960 W | |
DC input | Rated input voltage | 24 VDC | ||
Input voltage range | 23 to 28 VDC | |||
Input maximum current | for rated input voltage | 21.5 A | 43.5 A | |
for rated loads connected | ||||
Input terminal | Push-in terminal block | |||
Input protection | Fuse (cannot be replaced by the customer | |||
Input protection capacity | 30 A | 60 A | ||
DC output | Rated current | for rated output voltage | 20 A | 40 A |
Switching time | Uninterrupted | |||
Output voltage | Normal operation | Input voltage through output | ||
Backup operation | 21 to 28 V (the voltage cannot be adjusted) | |||
Output terminal | Push-in terminal block | |||
Overload protection | Warning display
UPS output will continue through bypass [during normal operation] UPS output will continue through battery [during backup operation] |
101% or more | ||
Output stopped by overload protection
Stop output [during normal operation] The internal power supply to the UPS will stop after 10 sec. [during backup operation] |
111% or more | |||
Warning display cancellation (During normal operation, during backup operation) | 93% or more | |||
Battery unit | Type | Lithium-ion battery | ||
Rated voltage | 25.2 VDC | |||
Rated capacity | 3900 mAh | 7800 mAh | ||
Battery life expectancy | 10 years (25°C), 6.7 years (35°C), 3.7 years (45°C), 1.9 years (55°C) | |||
Replacement by user | Yes (Hot swapping) | |||
Battery Life Counter Function | Yes | |||
Charging time | 8 hours (90%) | |||
Backup time (25°C, initial characteristics) | 6 min. (constant power rated load)
The backup time can be set from the mode selection / backup operation time selection switch, or the shutdown software. |
|||
Environment | Operating environment temperature / humidity | 0 to +55°C/10% to 90% RH with no condensation | ||
Storage environment temperature / humidity | −20 to +55°C/10% to 90% RH with no condensation | |||
Vibration resistance | JIS C 60068-2-6 compliant
5 to 8.4 Hz amplitude: 3.5 mm, 8.4 to 150 Hz Acceleration rate: 9.8 m/s² X, Y, and Z directions: 100 min. (Sweep time: 10 min.×Sweep count 10 times=Total: 100 min.) |
|||
Shock resistance | JIS C 60068-2-27 compliant: 147 m/s² X, Y, and Z directions three times | |||
Structure | Dimensions (W×H×D mm) | 44 × 124 × 111.4 (UPS control unit 20 A) | 52 × 124 × 111.4 (UPS control unit 40 A) | |
80 × 124 × 111.4 (battery unit 20 A) | 150 × 124 × 111.4 (battery unit 40 A) | |||
Weight | Weight of control unit | Approx. 0.6 kg | Approx. 0.7 kg | |
Weight of battery unit | Approx. 1.5 kg | Approx. 2.5 kg | ||
Cooling method | Natural cooling | |||
Dielectric breakdown voltage | Withstand voltage | DC external terminals to casing: 510 VAC, 1 minute, leakage current 5 mA max. | ||
Insulation resistance | DC external terminals to casing: 20 MW or more. (500 VDC) | |||
Standard compliance | Safety standard | UL508 / CE / C22.2 No. 107.1-01 | ||
EMI | Radiation disturbance field strength | EN61000-6-4 / FCC / ICES / RCM | ||
Internal power consumption
(normal/maximum) |
7 W/29 W | 15 W/58 W | ||
Serial communication | RS-232C (Interface terminal) | Yes (RJ45) | ||
USB (Interface terminal) | ||||
I/O signal (Interface terminal) | Yes (RJ45) | |||
Accessories | USB cable (2.2 m) (included with control unit)
Battery connection cable (included with battery unit) |
|||
Accessory functions | Remote ON/OFF signal logic setting; Battery life counter setting; Maximum backup time setting; Startup battery level setting; Backup stop (BS) signal delay time setting; and Backup (BU) signal delay time setting |
Backup time table (Time unit: minutes)
For devices that use the A indication, convert the capacity into W: W=A × 24
Model | Capacity (Watt) | |||||||||||||||||
30 | 60 | 90 | 120 | 180 | 240 | 300 | 360 | 420 | 480 | 540 | 600 | 660 | 720 | 780 | 840 | 900 | 960 | |
480W
(S8BA-24D24D480SBF + S8BA-S480L) |
134 | 63 | 41 | 29 | 19 | 15 | 11 | 9 | 8 | 6 | − | − | − | − | − | − | − | − |
480W
(S8BA-24D24D480SBF + S8BA-S960L) |
290 | 138 | 94 | 66 | 43 | 30 | 24 | 20 | 16 | 14 | − | − | − | − | − | − | − | − |
960W
(S8BA-24D24D960SBF + S8BA-S960L) |
290 | 138 | 94 | 66 | 43 | 30 | 24 | 20 | 16 | 14 | 13 | 12 | 11 | 10 | 9 | 8 | 7 | 6 |
Note: These backup times are for reference only. Times may vary according to battery life and external environmental conditions (temperature, etc).